Avanti DCU 400V

R1,009.00

Availability: 6 in stock (can be backordered)

- +
SKU: 300-DCU/140STR Category:


To control water levels in dams and reservoirs over long distances.


One Float Switch – 2 wire control


When the float contact is closed between terminals 5+7, the relay is energised.


On opening the float contacts the relay will de-energise.


Two Float Switch – 3 wire control:


For correct operation the Stop float must first close between terminals 6+7.


On this closure the Stop relay (STR) energises and makes contact between terminals 2+8.


The Start float is connected between 5+6 and on closure energises the ON relay.


This relay remains energised until the Stop float opens between 6+7.


The ON and STR relays are then both de-energised.


The STR relay is used for switching the electrical supply ON or OFF to the pump relay circuitry in the control panel.


Float terminal volts = 24V DC.


Distance: up to 4 km using 1.5mm copper wire/cable.


If more than one DCU is installed, interconnection of the outputs must be avoided.

MPN

300DCU140STR